HIGHvulnerability·

CVE-2025-41450: Danfoss AK-SM 800A Series Improper Authentication Vulnerability Actively Exploited

CVE-2025-41450 is an improper authentication vulnerability affecting Danfoss AK-SM 800A Series industrial control systems. This flaw allows an unauthenticated attacker to generate a web report exposing sensitive operational technology (OT) information, including internal IP addresses, usernames, and store names. The vulnerability is actively exploited, posing a significant risk to critical infrastructure.

This report was researched and drafted by an AI agent and reviewed by a human analyst prior to publication. View the agent workflow →
Indicators of Compromise(3)
↓ Download STIX
IP188.208.141.210
IP178.83.226.215
IP37.16.75.128

Overview

CVE-2025-41450 is a high-severity improper authentication vulnerability impacting Danfoss AK-SM 800A Series refrigeration controllers. This flaw enables an attacker to bypass authentication mechanisms and generate a web report containing sensitive data such as internal IP addresses, usernames, and store names. The vulnerability is actively exploited in the wild, making it a critical concern for organizations utilizing these devices, particularly within critical infrastructure sectors.

Technical Analysis

This vulnerability, tracked as CVE-2025-41450 and classified as CWE-305 (Improper Authentication), affects Danfoss AK-SM 8xxA Series devices prior to version 4.2. An attacker can exploit this flaw to:

  • Generate a web report without proper authentication.
  • Expose sensitive information, including:
    • Internal IP addresses
    • Usernames
    • Store names

The vulnerability has a CVSS 3.1 score of 8.2 (High) with the vector CVSS:3.1/AV:N/AC:H/PR:N/UI:R/S:C/C:H/I:L/A:H. While the attack vector is Network (AV:N), the attack complexity is High (AC:H), and user interaction is required (UI:R). However, successful exploitation leads to high confidentiality impact (C:H) and low integrity impact (I:L), with high availability impact (A:H) due to potential system disruption or information leakage.

Detection

Detecting exploitation of CVE-2025-41450 primarily involves monitoring web server logs on affected Danfoss devices or network traffic to them.

  • Web Server Logs: Look for unusual or unauthenticated access attempts to report generation endpoints or administrative interfaces. Specific URI paths related to report generation (e.g., /reports, /data_export, /admin/report) accessed without valid session tokens or from unexpected source IP addresses.
  • Network Traffic Analysis: Monitor for unusual HTTP requests targeting Danfoss AK-SM 800A devices, especially those originating from external or untrusted networks. Look for patterns indicative of information gathering, such as repeated requests to specific URLs that might trigger data exposure.
  • Authentication Failures/Bypasses: While the vulnerability is an improper authentication, successful exploitation might not always log as a failure. However, an increase in successful access to sensitive endpoints from unauthenticated sources could be an indicator.

Sigma Detection Rules

⚠️ AI-generated detection rules. These are experimental starting points. Review field names, EventIDs, and logic against your environment’s schema before deploying. Tune to reduce false positives.

Danfoss AK-SM 800A Suspicious Web Report Access

title: Danfoss AK-SM 800A Suspicious Web Report Access
id: 902b7a12-f0b4-4e78-8d01-1e9f1a0b2c3d
status: experimental
description: Detects suspicious access patterns to report generation endpoints on Danfoss AK-SM 800A devices, potentially indicating exploitation of CVE-2025-41450.
logsource:
  product: webserver
  service: access
detection:
  selection:
    cs-uri-stem|contains:
      - '/report'
      - '/data_export'
      - '/admin/report'
      - '/api/v1/reports'
  condition: selection
level: medium

Mitigations

  1. Patch Immediately: Upgrade Danfoss AK-SM 8xxA Series devices to version 4.2 or later to address the improper authentication vulnerability.
  2. Network Segmentation: Isolate Danfoss AK-SM 800A devices on a dedicated network segment, restricting all unnecessary inbound and outbound network traffic. Prevent direct exposure to the internet.
  3. Access Control: Implement strict access controls, limiting network access to the device’s web interface only to authorized management workstations and personnel.
  4. Monitor Logs: Regularly review web server and network logs for suspicious activity, as outlined in the Detection section.
  5. Secure Configuration Review: Ensure all devices are configured with strong, unique passwords and disable any unnecessary services or features.

References

  • https://nvd.nist.gov/vuln/detail/CVE-2025-41450
  • https://www.danfoss.com/en/service-and-support/coordinated-vulnerability-disclosure/danfoss-security-advisories/dsa-2025-03-01/
  • https://github.com/msuiche/fromagegate
  • https://www.cisa.gov/known-exploited-vulnerabilities-catalog?field_cve=CVE-2025-41450
  • https://dti.domaintools.com/research/european-refrigeration-systems-cyber-sabotage
  • https://www.sekoia.com/blog/the-cold-chain-on-fire-unpatched-danfoss-controllers-exploited
  • https://ltna.com.au/cyber
  • https://www.cisa.gov/news-events/alerts/2026/11/25/cisa-adds-10-known-exploited-vulnerabilities-catalog#main
  • https://www.cve.org/CVERecord?id=CVE-2023-25914
  • https://claroty.com/team82/research/freeze-the-controller-defrost-the-food-uncovering-vulnerabilities-in-danfoss-refrigeration-controllers

Indicators of Compromise

Type Value Description
IP Address 178.83.226.215 IP address used in exploitation attempt against honeypots (via https://www.sekoia.com/blog/the-cold-chain-on-fire-unpatched-danfoss-controllers-exploited)
IP Address 188.208.141.210 IP associated with reconnaissance and attempted authentication against a Danfoss honeypot (via https://dti.domaintools.com/research/european-refrigeration-systems-cyber-sabotage)
IP Address 37.16.75.128 IP address used in exploitation attempt against honeypots (via https://www.sekoia.com/blog/the-cold-chain-on-fire-unpatched-danfoss-controllers-exploited)

MITRE ATT&CK

  • T1592.001 — Hardware
  • T1589.001 — Credentials
  • T1589.002 — Email Addresses
  • T1592 — Gather Victim Host Information
  • T1133 — External Remote Services
  • T1489 — Service Stop
  • T1082 — System Information Discovery
  • T1071 — Application Layer Protocol
  • T1190 — Exploit Public-Facing Application
  • T1567 — Exfiltration Over Web Service
  • T1589 — Gather Victim Identity Information
  • T1491 — Defacement
  • T1595 — Active Scanning
  • T1548 — Abuse Elevation Control Mechanism
  • T1210 — Exploitation of Remote Services
  • T1110 — Brute Force
  • T1565 — Data Manipulation
  • T1078 — Valid Accounts
  • T1499 — Endpoint Denial of Service
  • T1496 — Resource Hijacking
  • T1485 — Data Destruction
  • T1498 — Network Denial of Service
  • T1018 — Remote System Discovery
  • T1590 — Gather Victim Network Information
  • T1200 — Hardware Additions
🤖 AI Attribution
Generated by gemini-2.5-flash ·
2,314 input / 1,575 output tokens ·
Reviewed and approved by a human analyst before publication
#vulnerability#critical-infrastructure#cve#danfoss#high#ics#improper-authentication#information-disclosure#ot#vulnerability